PyPowSyBl import#

The PyPowSyBl import path is the supported path for CGMES import and for parallel PST group identification.

When grouped PST optimization is enabled downstream, parallel PST groups are derived during DC solver preprocessing from the Powsybl grid data. PSTs are considered part of the same supported group only when they connect the same voltage magnitude, share the same bus pair regardless of orientation, and have matching tap and phase-shifter parameters. The derived group metadata is persisted into the processed grid artifacts and later written to action_set.json as pst_ranges[*].pst_group.

pypowsybl_import

Branch masks#

The importer writes these branch masks to masks/ for lines, transformers (trafo, trafo3w) and tie lines. Switches have the same two masks for monitoring.

File Meaning
*_for_nminus1.npy The element is outaged as a single-element contingency.
*_for_optimized.npy The element is monitored and healed if it exceeds its limit (optimized).
*_for_non_worsening.npy The element is monitored, is not healed and must not get worse (non-worsening). Set for border lines and tie lines, and for DSO transformers.

The monitored elements are the union of the optimization and non-worsening masks, see Monitored branches. The optimization limit of each monitored branch depends on its mask, see Artificial limits.

N-1 definition#

The importer saves an N-1 definition next to the processed grid (nminus1_definition.json). It is built in the same order in two journeys, depending on whether input_nminus1_definition_file is set in the importer parameters:

Stage Input N-1 definition given No input N-1 definition
1. Source The input definition, validated against the grid before the three-winding transformer conversion Derived from the grid file through the network masks
2. Area settings The input definition is authoritative and not filtered. Network reduction keeps the voltage levels of all its elements. View area, N-1 area and cutoff voltage, applied through the masks
3. Transformer conversion Three-winding transformers are replaced by their three two-winding legs Same

Without an input definition, every element selected by a *_for_nminus1 mask becomes a single-element contingency. The switch_for_nminus1 mask is always empty: opening a single switch usually only de-energizes the equipment behind it, which an AC loadflow cannot solve. Switches selected by switch_for_optimized or switch_for_non_worsening are still monitored. The busbars and couplers of the relevant stations (relevant_subs) are monitored as well, taken from the asset-topology master data.

The importer splits the monitored branches into two masks that it never sets for the same element (the DC solver itself accepts an element in both, which then counts as optimized). Branches in the view area with operational limits are optimized (*_for_optimized): they are healed if they exceed their limit. Lines and tie lines leaving the N-1 area, and every DSO transformer (only one side at or above the cutoff voltage), are non-worsening (*_for_non_worsening): they are not healed but must not get worse. Border branches without limits are only non-worsening if border_line_factors or dso_trafo_factors is set, because the limits are then derived from the loadflow. Blacklisted lines are not monitored, DSO transformers are exempt from the blacklist.

With an input definition, the converted definition is finally checked against the processed grid again, dropping elements that later preprocessing steps removed. Either way, every element id in the saved definition exists in the saved grid. The network masks are computed in both journeys, so control area settings such as switchable stations still apply.

Input N-1 definition#

An input (or business) N-1 definition is a Pydantic JSON dump of Nminus1Definition whose element ids were already resolved by its producer. load_nminus1_definition_for_network loads it and passes it to filter_nminus1_definition_to_network. The validation is soft and logs a warning for every change:

  • Elements that are not in the grid are dropped from contingencies and monitored elements.
  • Elements whose type or kind differs from the grid are corrected to the grid's values.
  • Contingencies that lose all their elements are dropped. The empty base case is kept.
  • SPPS rules are dropped as a whole if their contingency was dropped or if any condition or action element is not in the grid.

Three-winding transformers are referenced by their original id, which is why this validation runs on the grid before the conversion.

The input and the saved definition are two separate files. input_nminus1_definition_file is read from the same filesystem as the grid model file. The grid-validated result is always written to nminus1_definition.json in the data folder, which is the file AC contingency analysis and the optimizer read. Do not store the input file at that path: if both filesystems point to the same location, the import overwrites it.

An example input definition for the complex test grid is create_complex_grid_nminus1_definition.

Three-winding transformer conversion#

The importer replaces every three-winding transformer <id> by the two-winding transformers <id>-Leg1, <id>-Leg2 and <id>-Leg3. convert_three_winding_transformers_in_nminus1_definition rewrites the N-1 definition to match:

  • A contingency or monitored element on <id> becomes the three legs, in place.
  • An SPPS condition or action on <id> is copied once per leg, regardless of the rule's condition logic. Under ANY logic the rule therefore triggers as soon as one leg meets the condition.
  • Legs that are already listed are not duplicated, so the conversion can safely be applied twice.

If network reduction cuts through a transformer, only the legs left in the reduced grid are used.