CRAC generation parameters#
Parameters used by TopRAO to filter the monitored elements and create remedial actions from the elements present in the grid.
Parameters#
affectedCnecMinActivePowerDiff#
A branch is monitored in the RAO for a specific contingency if:
Default value is 5 (in MW).
affectedCnecMinLoadingDiff#
A branch is monitored in the RAO for a specific contingency if:
Where \(Loading_{state}\) is the ratio of the current (or active power) on the branch over the current (or active power) limit on the branch.
Default value is 0.1
pstActions#
Whether PST actions should be enabled.
Default value is true.
pstTapChangeMaxUp#
Maximum taps change allowed for the optimizer in direction "up".
Default value is 3.
pstTapChangeMaxDown#
Maximum taps change allowed for the optimizer in direction "down".
Default value is 3.
redispatchActions#
Whether redispatch actions on generators should be enabled.
Default value is true.
redispatchGeneratorRequiredMaxP#
Minimal value of generator's maxP required to be considered in redispatch actions (in MW).
Default value is 17.5
redispatchActivationCost#
Activation cost of a generator.
Default value is 100
redispatchCostUp#
Cost of 1 MW change up on a generator.
Default value is 1
redispatchCostDown#
Cost of 1 MW change down on a generator.
Default value is 1
rangeActionsCountries#
Countries for which PSTs and generators actions are created.
Default value is all countries.
limitMultiplierPreventive#
Multiplier applied on branches' limits for preventive state.
Default value is 1
limitMultiplierOutage#
Multiplier applied on branches' limits for outage state.
Default value is 1
limitMultiplierCurative#
Multiplier applied on branches' limits for curative state.
Default value is 1
JSON representation#